Master Control module supervises up to eight engine-generators.
Options include a redundant processor for added reliability and capacity to manage up to 64 automatic transfer switches.
The main bus is available in amperages of 3000, 6000 and 10,000 at 100KAIC.
A 12 in. touch screen for controlling the power system is standard.
|
|
Single Generator With Master Control module provides the same capabilities as the Master Control module and includes controls and a breaker for a single generator.
It is a space-saving, compact solution for power systems with an odd number of generators.
It accommodates your circuit breaker of choice and includes 100KAIC, LSIA function with an electronic trip unit.
This module also is available as a Single Generator, without Master Control. The Single Generator module is used in three engine-generator systems that require a redundant master controller.
|
Dual Generator module provides controls and circuit breakers for two engine-generators.
It is a space-saving, cost-effective solution for power systems with up to eight generators.
The main bus is available in amperages of 3,000, 6,000 and 10,000 at 100KAIC.
It accommodates your circuit breaker of choice and includes 100KAIC, LSIA function with an electronic trip unit. A 12 in. touch screen is optional.
|
|