Product Features |
|
|
- Nominal voltage 120/240 V 60 Hz, single phase.
- Listed to UL1008 Transfer Switch Equipment and CSA Certified to CSA 22.2 No. 178-1978 Automatic Transfer Switches.
- Meets National Electrical Code (NEC) and National Fire Protection Association (NFPA) requirements.
- True double-throw contacts (no intentional off position), with inherent mechanical interlocking to prevent connection of generator and utility source.
- Convenient terminals to connect neutral and ground conductors from service and load feeders.
- Available in Type 1 (indoor) and Type 3R (outdoor) enclosures.
- Manually-operated Series 165 Transfer Switches are also available.
- Available from stock.
|
|
 |
|
|
|
|
| Time Delay Functions |
|
- 3-second time delay to override momentary utility source.
- 15-second transfer to emergency time delay to allow engine generator to stabilize after starting.
- 15-second time delay after transfer to the standby source to ignore momentary voltage dips on the generator during initial loading.
- 5-minute time delay on retransfer to allow utility source to stabilize prior to transferring the load back to utility.
- 1-minute unloading running time delay for engine generator cool-down before shutdown.
|
|
|
|
|
|
|
|
| Control Panel |
|
 |
|
 |
|
|
|
Diagnostic Indicators |
|
|
|
|
|
The 165 Automatic Transfer Switch has a unique built-in automatic digital diagnostic monitoring system, which provides status on potential system problems such as: generator failed to start; generator over frequency; transfer switch did not transfer; and more. It's one more way you can count on ASCO to provide continuous power protection ...anytime. |
|
|
|
|
|
|
 |
|
 |
 |
|
|
|
|
|
|
|